0.6~1kV cross-linked polyethylene insulated power cableProduct number:YJV~YJV73 0.6~1
Advisory
Product Usage:
This product is suitable for power transmission in the power lines ratedat 1kV and below. Suitable for laying in hotels, railway stations, chemicals,oil platforms, mines, power plants, subways, high-rise buildings and otherfixed laying places.
Implementation standards :
Implementation of GB / T12706.1.
For ordinary flame-retardant power cables, but also the implementationof GB / T 19666, the flame retardant properties in line with GB / T 18380requirements;
For anti-termite cable power cable its anti-termite properties in linewith JB / T 10696.9 requirements
Model name andpurpose:
Note: 1、For flame-retardant powercable, “Z(ZA-、ZB-、ZC-)” is added before the above type number;anti-termite power cable, "FY-" is added before the abovetype number;intelligent on-line temperature monitoring cable, "DFTS-"is added before the above type number.
2、single-corearmored cable for the exchange system, should be non-magnetic material armored.
Product specifications:
Use features:
1、Maximumrated temperature
Long-termmaximum allowable operating conductor temperature: 90 °C,Maximum operatingtemperature under short-time overload: 130°C,Maximum operating temperatureunder short circuit (short circuit duration 5 s): 250 °C
2、Requirements:
2.1 Cable laying shall not be restricted by drop height;the ambient temperature for laying shall not be lower than 0 °C, and if theambient temperature is lower than 0 °C, the cable shall be pre-heated.
2.2 Minimumbending radius of cable